Is there a CE compliance issue with attaching electrical components to a hinged door? For ease of construction, we often attach components to the access door of our industrial control panel enclosures. We are being told by a customer that, for compliance with CE, electrical components are never allowed on a door. Is the inspector exercising personal preference, or is there a compliance standard that backs up this decision to reject our wiring practices? Open
EN 60204-1 clause 11.2.1 states:
"No devices except devices for operating, indicating, measuring, and cooling shall be mounted on doors or on normally removable access covers of enclosures."
Going beyond the limit imposed by the above quoted clause is generally to be discouraged, but it's perfectly possible to meet the EHSR's of the LVD or Machinery Directives if other mitigating measures are applied.
The provision of insulation to prevent finger access to any dangerous parts and marking on the outside of the panel are two examples of such measures.
Such a door should be separately earthed and not be reliant upon hinges for earthing.