Published 13/10/26
It is commonplace in industrial settings for linked machinery to be placed in separate rooms or multiple areas of a factory. But what happens when these areas cross different fire zones? In these instances, engineering a line that passes through a wall becomes a complex legal puzzle. At a point where competing pieces of legislation overlap, which should take priority?
We recently worked with a client to negotiate this regulatory grey area. On one side, you have building regulations and fire safety approved documents requiring suitable compartmentalisation. On the other, you have strict Machinery Legislation demanding operator and functional safety.
Their initial design involved a retractable conveyor, which in the event of a fire alarm, moved out of the way of a fire shutter door. While this seemed like a logical engineering fix, it quickly became evident that satisfying one piece of legislation meant violating another, making full compliance with both regulatory areas impossible.
Questions arose when considering both areas of legal requirements.
- The Power Dilemma: What happens in a power cut? Automatic release mechanisms for fire door sets must close when electricity supply fails, the same must be true for the conveyor retraction.
- The Maintenance Conflict: What happens if the conveyor is under maintenance when the fire alarm triggers? If a technician has locked out the machine for safety, the fire shutter is blocked from closing.
- The Functional Safety Gap: Standards for the reliability of control systems for machinery use a different approach to the reliability of automatic release mechanisms for fire doors. How can the reliability of the complete system be specified or verified?
- Control Priority: The emergency stop (category 0) for the retracting mechanism and the safe state for the fire compartmentalisation are in conflict. If the fire system triggers the conveyor to retract, should an E-stop take priority? Conversely, if the machine is already E-stopped, should the fire system still be allowed to override it and force a retraction?
Whilst a technical solution appears obvious and possible, only when both product safety legislation and fire regulations are considered can you foresee the issues.
For system integrators and those implementing production lines across a factory, at what stage would you identify this regulatory conflict? Where else have you experienced safety issues where the standards and directives don’t align leaving you in a legal and compliance cul-de-sac?